Experimental analysis of defrosting and heating performance of a solar-assisted heat pump integrated phase change energy storage

Chen, Haifei, Li, Guiqiang, Wang, Yunjie, Zhang, Fuwei, Badiei, Ali orcid iconORCID: 0000-0002-2103-2955, Lu, Tao, Yang, Jie, Jiang, Lvlin and Zhang, Yang (2020) Experimental analysis of defrosting and heating performance of a solar-assisted heat pump integrated phase change energy storage. International Journal of Energy Research, 44 (3). pp. 2173-2182. ISSN 0363-907X

[thumbnail of Author Accepted Manuscript]
Preview
PDF (Author Accepted Manuscript) - Accepted Version
Available under License Creative Commons Attribution Non-commercial No Derivatives.

1MB

Official URL: https://doi.org/10.1002/er.5076

Abstract

This thesis investigates a novel solar-assisted heat pump integrated phase change energy storage system. The defrosting performance of this system was studied experimentally and the results were compared with two traditionally used methods: reverse cycle defrosting (RCD) method and hot gas bypass defrosting (HGBD) method. The results show that the phase change energy storage system has superior performance compared with traditional defrosting methods. The indoor temperature drop recorded was relatively small and the defrosting time was 75% of the RCD system and 53% of HGBD system. The phase change energy storage system increased the condensation temperature which consequently increased the temperature difference of heat transfer resulting in higher conductivity in the defrosting progress. Compared with the method of RCD and the method of HGBD, the recovery time of the system was shortened by 90 and 160 seconds, respectively. The system works with low-temperature heat source and circulating water, which considerably reduces energy consumption, thereby improving the performance of the defrosting system. A further experimental study was also conducted on the heating performance and the results also indicated that the value of COP can reach up to 3.6 in daytime, and the indoor temperature can be stably maintained above 18°C throughout the day.


Repository Staff Only: item control page